Liquid Extractor-Injector Kit Anova
- Liquid extractor-injector kit Anova
€28.70 VAT incl.
The Diesel Generator Set Genergy GDS130T 127 kVA has a rated power of 115 kVA / 92 kW, a maximum power of 127 kVA / 101 kW, dimensions of 2450x1050x1350 mm, and voltage of 400 V.
The fuel consumption of this generator is 5.80l/h - 12.10l/h - 17.60l/h - 23.40l/h at 25% 50% - 75% - 100% of its power respectively. Its current type is three-phase, it has an electronic stabilization system "AVR" and is equipped with a copper coil.
The Diesel Generator Set Genergy GDS130T 127 kVA with a displacement of 6490 cc, provides us with a fuel tank capacity of 200 L. It has a frequency of 50 Hz, a weight of 1620 Kg, and its average sound pressure is 75 dB.
GENERATOR MODEL | GDS130T (REF 21095) |
Stabilization system | AVR" electronics |
Voltage - Frequency | 400V - 50Hz |
Maximum Power | 115 kVA (92kW) |
Nominal Power | 127 kVA (101kW) |
Power Factor | 0.8 |
Nominal current | 166 A |
Average sound pressure at 7Mts LpA | 75 dB |
Guaranteed sound power level LwA 2000/14/EC Amendment 2005/88/EC | 97 dB |
Start-up type | Electric |
Fuel tank capacity | 200 L |
Fuel consumption 25% 50% 75% 100% (L/H) | 5.80 - 12.10 - 17.60 - 23.40 |
General protection degree | IP23 |
Dimensions | 2450x1050x1350 mm |
Weight | 1620 Kg |
ALTERNATOR | SINC274DX |
Nominal speed - Number of poles | 1500RPM - 4 |
Excitation system | Self-excited |
Phases | Three-phase |
Total harmonic distortion | No load |
Telephone interference | >2% |
Efficiency | 90.8% |
Insulation grade | H |
Degree of protection | IP23 |
MOTOR | GENERGY-SDE6105ZLDT |
Displacement | 6490 cc |
Speed control | Electronic |
Number of cylinders and arrangement | 6 in line |
Injection system | Direct |
Aspiration | Turbocharged |
Cooling system | Water |
Diameter X Stroke | 110x125 mm |
Engine power | 110 kW |
Lubrication oil capacity | 16L (SAE10W40) |
Coolant capacity | 24 L |
IMPORTANT NOTICE |
It is mandatory for the customer to check oil and grease levels before start-up. If it is not possible to check the goods at the time of receipt, it must be indicated on the carrier's sheet that the customer is in agreement except for pending examination. |
Data sheet
Specific References